This unit senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of 4°F to 158°F, and a humidity range of 0 to 95 percent (noncondensing). A plug-in sensor head offers superior false alarm immunity. These features, plus a NEMA 4 rating, allow operators to mount the detector to rooftop HVAC equipment or use the detector in other harsh environments. The new design provides the same form, fit, and wiring terminations as the standard InnovairFlex unit. Superior test and operational features added to the standard model are also available in this watertight unit. As the only watertight duct smoke detector on the market, D4120W provides unsurpassed environmental protection while simplifying installation, testing, and maintenance. This InnovairFlex duct smoke detector can be customized to meet local codes and specifications without additional wiring. The new InnovairFlex product line is compatible with all previous Innovair models, including remote test accessories. : Duct smoke detectors have specific limitations. DUCT SMOKE DETECTORS ARE: NOT a substitute for an open area smoke detector, NOT a substitute for early warning detection, and NOT a replacement for a buildings regular fire detection system. Refer to NFPA 72 and 90A for additional duct smoke detector application information. Size: (Rectangular) - 14.38 in (37 cm) Length; 5 in (12.7 cm) Width; 2.5 in (6.36 cm) Depth (Square) - 7.75 in (19.7 cm) Length; 9 in (22.9 cm) Width; 2.5 in (6.35 cm) Depth Weight: 2.5 lb (1.14 kg) Operating Temperature Range: -4°F to 158°F (-20°C to 70°C) Storage Temperature Range: 22°F to 158°F (30° to 70°C) Operating Humidity Range: 0% to 95% relative humidity non-condensing Air Duct Velocity: 100 to 4000 ft/min (0.5 to 20.32 m/sec) NEMA Enclosure Rating: Type 4 - Watertight Indoor/Outdoor View Full Specifications |