Product Type:Duct Detector|Input Voltage:24VDC|Detection Type:Photoelectric|Connection Type:System|Intended Use:Commercial/Industrial|Battery Backup:No|Interconnect:No|System Type:Addressable

Features

  • ETL listed to UL 864, ULC 527, and ULC 559
  • Photoelectric, integrated low-flow technology (HFS-DPRdetector head included)
  • Air velocity rating from 100 ft/min to 4000ft/min (0.5m/s to20.32m/sec)
  • Versatile mounting options: square or rectangular configuration
  • Broad ranges for operating temperature (-4°F to 158°F) andhumidity (0% to 95% non-condensing)
  • Patented sampling tube installs from front or back of thedetector with no tools required
  • Cover tamper signal
  • Increased wiring space with a newly added 3/4-inch conduitknockout
  • Available space within housing to accommodate mountingof relay module
  • Easily accessible code wheels on sensor head
  • Clear cover for convenient visual inspection
  • UL 268A listed
  • Remote testing capability
  • Requires com line power only

Description

The HFS-D is flexible enough to fit mounting configurationsfrom square to rectangular and everything in between.

The HFS-D intelligent non-relay photoelectric duct smokedetector features a pivoting housing that fits both square andrectangular footprints capable of mounting to a round or rectangularduct. This unit senses smoke in the most challengingconditions, operating in airflow speeds of 100 to 4000 feet perminute, temperatures of -4°F to 158°F, and a humidity range of0 to 95 percent (non-condensing).

An improved cover design isolates the sensor head from thelow-flow feature for simple maintenance. A cover tamper featurewas added to indicate a trouble signal for a removed orimproperly installed sensor cover. The housing provides a 3/4-inch conduit knockout and ample space to facilitate easy wiringand mounting of the HFS-MR relay module.

The HFS-D can be customized to meet local codes and specificationswithout additional wiring. The new HFS-D is compatiblewith various remote test accessories.

WARNING: DUCT SMOKE DETECTORSHAVE SPECIFIC LIMITATIONS.DUCT SMOKE DETECTORS ARE NOT ASUBSTITUTE FOR AN OPEN AREA SMOKEDETECTOR, NOT A SUBSTITUTE FOR EARLYWARNING DETECTION, AND NOT AREPLACEMENT FOR A BUILDINGS REGULARFIRE DETECTION SYSTEM.REFER TO NFPA 72 AND 90A FORADDITIONAL DUCT SMOKE DETECTORAPPLICATION INFORMATION.

Accessories

Accessory Current Loads at 24 VDC: RA100Z, RTS151/RTS151KEY 12 mA max in alarm; 0 mA in standby.

System Sensor provides system flexibility with a variety ofaccessories, including two remote test stations and differentmeans of visible and audible system annunciation. As with ourduct smoke detectors, all duct smoke detector accessories areUL listed (RTS151, RTS151KEY, RA100Z: UL S2522).

HFS-DPR Replacement photoelectric head for duct detector
DST1 Metal sampling tube duct width up to 1 ft (0.3 m)
DST1.5 Metal sampling tube duct widths 1 ft to 2 ft (0.3 m to 0.6 m)
DST3 Metal sampling tube duct widths 2 ft to 4 ft (0.6 m to 1.2 m)
DST5 Metal sampling tube duct widths 4 ft to 8 ft (1.2 m to 2.4 m)
DST10 Metal sampling tube duct widths 8 ft to 12 ft (2.4 m to 3.7 m)
P48-21-00 End cap for metal sampling tubes
RA100Z Remote annunciator alarm LED
RTS151 Remote test station
RTS151KEY Remote test station with key
DCOIL Remote test coil required with RTS151/RTS151KEY
M02-04-00 Test magnet
DH400OE-1 Weatherproof enclosure