The GD-6 is a versatile, easy-to-use device that allows you to select between methane, propane or hydrogen gas detection. It provides low-level detection of combustible gas in an easy-to-maintain monitor that is factory calibrated for simple installation.
This low voltage detector provides automatic feedback and fan control that can help reduce combustible gas concentrations in parking garages, maintenance facilities, and other locations that require combustible gas detection.
UPC | 0 00 51131 49886 0 |
Accuracy | ±5% of the LEL reading up to 50% LEL |
Power | 3 W (max) from 12 to 24 VAC or 12 to 48 VDC |
Current @ 24VDC | 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA stand by |
Shipping Weight | 1 pound (0.45 kg) |
Size | 4.5 x 4 x 2.125 in. (11.4 X 11.4 X 5.3 cm) |
Color | Dark gray |
Connections | Plugs/terminals |
Mounting Box | (Not included) 4x4 electric |
Fan Relay | 5 A, 240 VAC, pilot duty, SPDT |
Fan Relay Actuation | Selectable at 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 (default),11, 12, 13, 14, 15, 16,17, 18, 19, 20% LEL |
Fan Delay Settings | 0, 1, 3 (default), 5 and 10 minutes |
Fan Minimum Run Time | Settings are OFF (default), 3, 5, 10, 15 minutes |
Alarm Relay | 0.5A 200 V, 10 VA |
Alarm Relay Actuation | Selectable N.O. default or N.C. |
Alarm Relay Settings | OFF, 5, 10, 15, 20 (default), 25% LEL |
Current Loop | 4-20 mA for 0-50% LEL |
Operating Environment | 0° F to 125° F (-18° C to 52° C) 10 to 90% RH |