Altronix AL1012ULM Access Power Distribution Module w/ Power Supply/Charger, 5 PTC Class 2 Outputs, 12VDC @ 10A, FAI, 115VAC, BC400 Enclosure
Altronix AL1012ULM Access Power Distribution Module w/ Power Supply/Charger, 5 PTC Class 2 Outputs, 12VDC @ 10A, FAI, 115VAC, BC400 Enclosure

Altronix AL1012ULM Access Power Distribution Module w/ Power Supply/Charger, 5 PTC Class 2 Outputs, 12VDC @ 10A, FAI, 115VAC, BC400 Enclosure

Manufacturer:Altronix
Manufacturer Part#:AL1012ULM
Our Part#:AX-AL1012ULM
Stock Status: Altronix
Retail Price:$280.48
Your Savings:$29.92(11%)
Your Price:$250.56

Feature:

Altronix

Feature:

AX-AL1012ULM

Feature:

Yes
AL1012ULM multi-output access control power supply/charger is specifically designed for use with access control systems and accessories. This unit converts a 115VAC, 60Hz input into five (5) individually protected Class 2 Rated power limited 12VDC outputs. Each output will route power to a variety of access control hardware devices including Mag Locks, Electric Strikes, Magnetic Door Holders, etc. These outputs will operate in both Fail-Safe and Fail-Secure modes. Controlled trigger input is achieved through normally open (N.O.) or normally closed (N.C.) supervised input or the polarity reversal from an FACP (Fire Alarm Control Panel). A form "C" dry output relay enables HVAC Shutdown, Elevator Recall orit may be used to trigger auxiliary devices.

Input
Input 115VAC, 60Hz, 2.6A.
Input fuse rated @ 3.5A/250V.
Fire Alarm Panel or Access Control System trigger inputs. N.O. or N.C. supervised trigger input and polarity reversal trigger input.
Output
12VDC outputs.
10A supply current.
Five (5) PTC protected Class 2 Rated power limited outputs, rated @ 2A (auto-resettable).
Output relay energizes when unit is triggered (form "C" contact rated 1A @ 28VDC).
Filtered and electronically regulated output.
Short circuit and thermal overload protection.
Battery Backup
Built-in charger for sealed lead acid or gel type batteries.
Automatic switch over to stand-by battery when AC fails.
Supervision
AC fail supervision (form "C" contacts).
Notification trigger is selectable for 30 seconds (factory set) or 6 hours.
Low battery supervision (form "C" contacts).
Battery presence supervision (form "C" contacts).
Power fail supervision relay (form "C" contacts).
Visual Indicators
AC input and DC output LED indicators (power supply board).
Red LEDs indicate condition of power outputs (multi-output board).
Power & input trigger LEDs (multi-output board).
Temperature
Operating: 0° C to 49° C (32° F to 120° F).
Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity 85% +/- 5%.
BTU/Hr (approx.): 61 BTU/Hr.
System AC input VA requirement: 299VA.