Altronix AL1024ULXB2 UL Listed Sub-Assembly power supply/charger converts 115VAC, 60Hz input into a single 24VDC non-power-limited output. It also offers a suite of features that includes AC fail supervision, battery presence, and low battery supervision.
Input
Input 115VAC / 60Hz, 4.2A.
Output
24VDC output (UL 1481).
8A continuous supply current with 10A supply current during alarm (UL 1481).
24VDC @ 10A (UL 294).
Filtered and electronically regulated output.
Maximum Ripple: 250mV P/P.
Short circuit and thermal overload protection.
Battery Backup
Built-in charger for sealed lead acid or gel type batteries.
Maximum charge current 3.6A.
Automatic switch over to stand-by battery when AC fails.
Zero voltage drop when switched over to battery backup.
Visual Indicators
AC input and DC output LED indicators.
Supervision
AC fail supervision (form "C" contacts).
Low battery and battery presence supervision (form "C" contacts).
Additional Features
Short circuit and thermal overload protection.
Electrical
Temperature:
Operating: 0° C to 49° C (32° F to 120° F).
Storage: - 20° C to 70° C ( - 4° F to 158° F).
Relative Humidity 85% +/- 5%.
BTU/Hr (approx.): 123 BTU/Hr.
System AC input VA requirement: 483VA.
Mounting hardware included.