Feature:

Macurco

Feature:

MA-DVP-120

Feature:

Yes

Feature:

783748841226

Feature 5

Yes

Specifications

GSA

Feature 7

Detection Type:Ammonia,Carbon Monoxide,Hydrogen,Hydrogen Sulfide,Methane,Nitrogen Dioxide,Propane|Product Type:Controller|Input Voltage:120VAC,240VAC|Intended Use:Commercial/Industrial|Connection Type:System|Product Status:Current|Battery Backup:No
GSA logo

Features

  • 120-240 VAC input
  • Compatible with CM-6, GD-6 and TX-6 gas sensors
  • 12 analog (current loop) input channels.
  • Three 16A, 240VAC SPDT fan / alarm Relays
  • Each relay is configurable for delay before activation and minimum on time
  • Two 24VDC drivers for horn/strobe (250 mA max)
  • External keypad for user selection of the transducer/alarm display and setting the configuration
  • Externally visible LCD display showing the status of each transducer and relay
  • Externally visible system, alarm and relay status indicators
  • Up to three ventilation control zones can be defined
  • Each zone can be controlled based on transducer signals and/or time of day
  • Fail-safe operation can be implemented
  • Modular input and output connectors
  • Lockable NEMA 1 type enclosure
  • ETL Listed to UL 508A, LADBS Approved

Description

The DVP-120 exhaust fan controller, in conjunction with Macurco™ gas transducers, provides automatic controls to help maintain an acceptable environment in parking garages or other facilities. The DVP-120 system is designed to meet specifications for safety in enclosed parking garages, including the Uniform Building Code and OSHA 50ppm CO requirements. The DVP-120 can control up to twelve gas sensors in any combination.

The DVP-120 exhaust fan controller which, in conjunction with CM-6 Carbon Monoxide Detectors, GD-6 Combustible Gas Detectors, TX-6-AM Ammonia Detector, TX-6-HS Hydrogen Sulfide Detector, or TX-6-ND Nitrogen Dioxide Detectors, provide automatic controls to ensure a safe environment in parking garages or maintenance facilities. The DVP-120 can control up to twelve sensors in any combination.

The DVP-120 system is designed to meet all known specifications for safety in enclosed parking garages, including the Uniform Building Code and OSHA 50 ppm CO requirements.

Compatible Detectors

Model# Detection Type Product Page
CM-6 Carbon Monoxide Open in New Window
GD-6 Combustible Gases Open in New Window
TX-6-AM Ammonia Open in New Window
TX-6-HS Hydrogen Sulfide Open in New Window
TX-6-ND Nitrogen Dioxide Open in New Window

Specifications

Power Input 90 - 250VAC @ 1A, 47-63 Hz, single-phase
Audible Indicator Internal buzzer, 90 dBA at 1ft
External Drivers (2) 24VDC, maximum 250 mA
Output Control Relays 3
Relay Ratings (3) SPDT, 120/240VAC, 10A resistive
LCD Display 2 rows of 16 characters with backlight
Status Indicators (LED) Power, ALARM/warning, Hush, Relay 1, Relay 2 & Relay 3
Operating Temperature 32° to 104°F (0° to 40°C)
CM-6 Transducer Range 0-200 PPM
GD-6 Transducer Range 0-50% LEL
TX-6 Transducer Range See specific TX model cut sheet
Relay On Delay 0 - 15 minutes in 1 second increments
Relay Off Delay 0 - 15 minutes in 1 second increments
Size (inches) 10.5" x 12.5" x 2"
Weight 6.5 lbs
Enclosure NEMA 1 Type
Accessories designed for use with this product - To add any of these accessories to your order, simply fill in the quantity you want and click the large "Add to Cart" button above