template image(0) Item / $0
8:00 AM - 4:00 PM EST (Monday-Friday) |Hi Guest, Login! |
Macurco GD-6 Gray Housing-Combustible Fixed Gas Detector & Controller
Macurco GD-6 Gray Housing-Combustible Fixed Gas Detector & Controller

Macurco GD-6 Gray Housing-Combustible Fixed Gas Detector & Controller

Manufacturer:Macurco
Manufacturer Part#:70-0716-0802-3
Our Part#:70-0716-0802-3
Stock Status: Drop Shipped
Retail Price:$1,160.85
Your Savings:$499.16(43%)
Your Price:$661.69

Feature:

Macurco

Feature:

70-0716-0802-3

Feature:

Yes

Feature:

051131498860

Feature 5

Yes

Feature 7

Detection Type:Propane,Methane|Product Type:Detector|Input Voltage:12VAC,12VDC,24VAC,24VDC|Intended Use:Commercial/Industrial|Connection Type:System|Product Status:Current|Battery Backup:No

Features

Combustible Gas Detection

  • Measures Methane (NG), Propane (LP) or Hydrogen (H2)
  • Low level meter capable of displaying from 0-50% LEL EX

Display, Control & Calibration

  • Selectable (on/off) digital display, buzzer, fan delay (minutes), fan minimum run time
  • Selectable fan and alarm relay activation
  • Factory calibrated. Can also be field calibrated using 10% LEL Methane, 10% LEL Propane or 10% LEL Hydrogen gas, regulator and calibration hood
  • One screw allows access for calibration

Installation

  • Mounts on a standard 4" x 4" electrical box, no cover needed
  • 5 A SPDT fan relay controls starters of exhaust fans
  • 0.5 A N.O. or N.C. alarm relay connects to warning devices or control panels
  • 4-20 mA current loop
  • Optional calibration kits allow the GD-6 to be tested and field calibrated using Methane, Propane or Hydrogen gas

Other Features

  • Supervised system design: internal detector problem will cause the fan & alarm relay to activate
  • ETL Listed to UL 61010-1

Description

The GD-6 is a versatile, easy-to-use device that allows you to select between methane, propane or hydrogen gas detection. It provides low-level detection of combustible gas in an easy-to-maintain monitor that is factory calibrated for simple installation.

This low voltage detector provides automatic feedback and fan control that can help reduce combustible gas concentrations in parking garages, maintenance facilities, and other locations that require combustible gas detection.

Selectable options include:

  • Measurement: Methane (NG), Propane (LP) or Hydrogen (H2)
  • Output: Fan relay, alarm relay and 4-20 mA current loop
  • Controls: Digital display (0-50% LEL), buzzer, fan delay, fan minimum run time

Specifications

UPC 0 00 51131 49886 0
Accuracy ±5% of the LEL reading up to 50% LEL
Power 3 W (max) from 12 to 24 VAC or 12 to 48 VDC
Current @ 24VDC 75 mA in alarm (two relays), 50 mA (fan relay only) and 23 mA stand by
Shipping Weight 1 pound (0.45 kg)
Size 4.5 x 4 x 2.125 in. (11.4 X 11.4 X 5.3 cm)
Color Dark gray
Connections Plugs/terminals
Mounting Box (Not included) 4x4 electric
Fan Relay 5 A, 240 VAC, pilot duty, SPDT
Fan Relay Actuation Selectable at 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 (default),11, 12, 13, 14, 15, 16,17, 18, 19, 20% LEL
Fan Delay Settings 0, 1, 3 (default), 5 and 10 minutes
Fan Minimum Run Time Settings are OFF (default), 3, 5, 10, 15 minutes
Alarm Relay 0.5A 200 V, 10 VA
Alarm Relay Actuation Selectable N.O. default or N.C.
Alarm Relay Settings OFF, 5, 10, 15, 20 (default), 25% LEL
Current Loop 4-20 mA for 0-50% LEL
Operating Environment 0° F to 125° F (-18° C to 52° C) 10 to 90% RH