The TX-12-HS has selectable 4-20 mA output, buzzer and digital display options. It is an electronic detection system used to measure the concentration of H2S and provide feedback and automatic exhaust fan control to help reduce H2S concentrations in refineries, pulp and paper mills, waste disposal or other commercial applications.
The TX-12-HS is a low level meter capable of displaying from 0-50 ppm of Hydrogen Sulfide. The TX-12-HS is factory calibrated and 100% tested for proper operation, but can also be calibrated in the field.
The TX-12-HS meets the NIOSH (National Institute for Occupational Safety and Health) and OSHA (Occupational Safety and Health Administration) standards for gas exposure.
Power | 100-240VAC (50 to 60Hz) |
Connections | Plugs/Terminals |
Current | 1.0A max |
Fan Relay | 5A, 240VAC, pilot duty, SPDT, latching or non-latching |
Fan Relay Actuation | Selectable at diS (disable), 2, 3, 4, 5, 6, 7, 8 (default), 9, 10 , 11, 12, 13, 14, 15, 16, 17, 18, 19, 20 ppm |
Fan Delay Settings | 0, 1, 3 (default), 5 and 10 minutes |
Fan Min. Runtime Settings | 0 (default), 3, 5, 10 or 15 minutes |
Alarm Relay | [email protected], 60VA |
Alarm Relay Actuation | Selectable N.O. (default) or N.C. |
Alarm Relay Settings | diS (disable), 5, 10, 15, 20 (default), 25, 30, 35, 40, 45, 50 ppm H2S |
Current Loop | 4-20 mA for 0-50 ppm H2S, selectable to off or on (default) |
Buzzer | 85dBA at 10 feet, selectable to off (default) or on |
Digital Display | 3 digit LED selectable to off (default) or on |
Operating Environment | 0°F to 125°F (-18°C to 52°C). 10 to 90% RH |
Operating Altitude | Up to 5,000m (16,404 feet) |
Mounting Box | 4" x 4" electrical box (not included) |
Size | 4½" x 4" x 2¾" (11.4 x 10.2 x 7 cm) |
Shipping Weight | 1 pound (0.45 kg) |
Color | Dark Gray |