Potter VSR-FE2-25, Vane-Type Waterflow Switch for 2.5-inch Steel Pipe, with Retard, DPDT Contact(s)
Potter VSR-FE2-25, Vane-Type Waterflow Switch for 2.5-inch Steel Pipe, with Retard, DPDT Contact(s)

Potter VSR-FE2-25, Vane-Type Waterflow Switch for 2.5-inch Steel Pipe, with Retard, DPDT Contact(s)

Manufacturer:Potter Electric
Manufacturer Part#:1116025
Our Part#:1116025
Stock Status: Call for Availability
Retail Price:$382.50
Your Savings:$88.27(23%)
Your Price:$294.23

Feature:

Potter Electric

Feature:

1116025

Feature:

Yes

Feature 5

No

Feature 7

Switch Type:Saddle-Type Flow Switch|Pipe Type:Steel|Nominal Pipe Size:2.5|Mounting Type:Saddle|Activation Type:Vane|Activation Delay (Retard):Yes|Contact Type:DPDT

Features

  • UL and ULC Listed, FM Approved
  • Service Pressure: Up to 450 PSI (31 BAR)
  • Minimum Flow for Alarm: 10 GPM (38 LPM)
  • Maximum Surge: 18 FPS (5.5 m/s)
  • Power Requirements
    • STANDBY: 10ma at 120V AC or 1.5ma at 24V AC/DC
    • ALARM: 40ma at 120V AC or 35ma at 24V AC/DC
  • Contact Ratings: DPDT (Form C) 2 Amps at 30VDC or 125VAC resistive
  • Conduit Entrances: Two knockouts provided for ½" conduit
  • Suitable for indoor or outdoor use with factory installed gasket and die-cast housing.
  • NEMA 4 Rated Enclosure - use with appropriate conduit fitting
  • Temperature range: 40°F / 120°F, 4,5°C/49°C
  • Non-corrosive sleeve factory installed in saddle
  • Sizes Available: Schedules 10 thru 40, sizes 2" thru 8" (50mm thru 200mm)
  • Caution: This device is not intended for applications in explosive environments.

Description

The Model VSR-FE-2 is a vane type waterflow switch for use on wet sprinkler systems. It is UL Listed and FM Approved for use on steel pipe; schedules 10 thru 40, sizes 2" thru 8" (50mm - 200mm). The unit may also be used as a sectional waterflow detector on large systems.

The unit contains an output relay and an adjustable electronic retard. The relay is actuated when a flow of 10 gallons per minute (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard period.

The unit is enclosed in a general purpose, die-cast housing. The cover is held in place with two tamper resistant screws which require a special key for removal. A fi eld installable cover tamper switch is available as an option which may be used to indicate unauthorized removal of the cover.

Compatible Pipe/Installation Requirements

ModelPipe SizeHole Size
 inchmminchmm
VSR-FE22501¼ + 1⁄8 - 1⁄1633 ± 2
VSR-FE2.52.5-
VSR-FE33802 ± 1⁄850 ± 2
VSR-FE3.53.5-
VSR-FE44-
VSR-FE55-
VSR-FE66-
VSR-FE88200