FEATURES
• Legend sheet protected by
scratch-resistant Lexan®
viewing window
• Durable steel frame mounts into
an Infinity Gang Box or standard
elect electrical back box and securely
holds the Infinity Gang Plate
• Standard legend slip sheet
and all mounting hardware
included
Equipped with a keyed or rotary
switch, this unit allows quick
control of your HVAC systems
like fans, dampers, and more.
SPECIFICATIONS
Compatible with all IAM and I Compatible with all IAM and IAV units. Every ICMHOA has a
black background with white screened legend and LED
point illumination in green and yellow. ControlS any HVAC
units requiring 24 VDC or dry contact interface. LEDs only
light after “positive feedback” is received from the field onto
TB2 in the form of a closed contact. If an ICMLEDTST is
installed, all of the LEDs should light when the switch is
activated, regardless of the state of an ICMENGAGE, if
installed. If an ICMLEDTST and an ICMENGAGE are part of
the control line, the ICMENGAGE must be wired electrically
after the ICMLEDTST. Standard clinch type terminal strip
used for field wiring.